Uninterruptible Power Products, Inc.
1567 W. 11th Drive Friendship, WI 53934
608.339.2151  800.832.7709  Fax:800.545.7623  www.uppi-ups.com
Home About Us What's New Products Batteries Services Dealers Forms Contact Us
Pioneer LineUPS - Uninterruptible Power Systems

 
Model: 20KVA 16KW
Base Price US
AC INPUT
Input ACV & Circuit Breaker requirements - hardwire connection only
Model # UPS 20-208 208VAC
125A
$15,870.00
Model # UPS 20-240 240VAC
110A
$15,870.00
Input Voltage Window  +15%, -20% of nominal VAC Input @ full load / +15%, -40% of nominal VAC Input @ 50% load
Frequency 60 HZ
Power Factor  .98
UNIT
Dim UPS HxWxD (in.) 70.5 x 28 x 24.5
Dim Battery Cab
HxWxD (in.)
.
56.5 x 18 x 24.5
Weight lbs. UPS 955
Wgt lbs. Battery Cab.  770

Efficency

92%
BTU's/Kw 3238/.950
Noise Attenuation 120db common mode, 60db transverse (normal) mode
Isolation Output is completely isolated from commercial power with less than 1 pf effective capacitive coupling primary to secondary. Secondary has neutral to ground bond, qualifying as a separately derived power source.
Surge Protection 6000 volts are suppressed to safe levels per ANSI/IEEE C62.41 - 1997 category A & B waveforms
Operating Temperature 0° to 40° C (32° to 104° F)
Relative Humidity 0 to 95% without condensation
High Altitude Operation Max. altitude 10,000 ft - de-rate 1° C off max operating temp per 1000 ft. about sea level
Agency Approvals UL 1778, cUL
User Interface Keypad w/LCD display, RS232 serial port, internal dial in modem, dry contact relays
Events Monitored Sags, Surges, Frequency Shifts, Voltage Spikes and Glitches are recorded and time/date stamped
 
AC OUTPUT
Output ACV-Hardwire  120 / 208 / 220 / 230 / 240
Output Receptacles  Optional (All types available - contact factory)
Output Waveform  Computer grade sine wave output power with less than 5% total harmonic distortion @ rated kw load. Sine wave correcting regardless of input voltage THD
Regulation  ±3% voltage regulation
Load Compatible  Guaranteed compatible with all loads including power factor corrected.
Overload  150% surge capability, overload alarm 101% load to 125% load for 10 min. before shutdown. Greater than 125% the system will shutdown in 5 seconds
Output Protection  Output ferroresonant transformer provides inherent current limiting protection
DC & INVERTER
Nominal DC Voltage  120VDC
Charger Amps  8A
Runtime (Full Load/Half Load)  10 min/25 min
Sound Level  55dBA
*Specifications subject to change without notice