| Pioneer
Power Conditioners |
| |
|
| Model:
10KVA
8KW |
Base
Price US |
| AC
INPUT |
| Input
ACV & Circuit Breaker requirements - standard connection
|
| Model
# PPC 8-208 |
208VAC |
70A |
$6,450.00 |
| Model
# PPC 8-240 |
240VAC |
60A |
$6,450.00 |
| Input
Voltage Window |
+15%,
-30% of nominal VAC Input @ full load / +15%, -40% of nominal
VAC Input @ 50% load |
| Frequency |
60
HZ |
| Input
THD |
5%
or less |
|
| UNIT |
| Dimension*
HxWxD
(in.) |
19.25
x 17.5 x 21.5 |
| Weight*
lbs. |
430 |
| Efficiency |
93% |
| BTU's
HR/Kw |
2055/.602 |
| Noise
Attenuation |
120db
common mode, 60db transverse (normal) mode |
| Isolation |
Output
is completely isolated from commercial power with less than
2 pf effective capacitive coupling primary to secondary. Secondary
has neutral to ground bond, qualifying as a separately derived
power source. |
| Surge
Protection |
6000
volts are suppressed to safe levels per ANSI/IEEE C62.41 -
1997 category A & B waveforms |
| Operating
Temperature |
0°
to 40° C (-4° to 104° F) |
| Relative
Humidity |
0
to 95% without condensation |
| High
Altitude Operation |
Max.
altitude 10,000 ft - de-rate 1° C off max operating temp
per 1000 ft. above sea level |
| Agency
|
UL
1778, cUL listed |
| User
Interface |
Keypad
w/LCD display, RS232 serial communications, dial in modem
|
|
|
| AC
OUTPUT |
| Output
AC Voltage |
120
/ 208 / 240 |
| Output
Receptacles |
Optional |
| Output
Waveform |
Computer
grade sine wave output power into resistive load. |
| Regulation |
±1%
voltage regulation |
| Load
Compatible |
Guaranteed
compatible with all loads |
| Overload |
150%
surge capability, overload alarm 101% load to 125% load for
10 min. before shutdown. Greater than 125% the system will
shutdown in 5 seconds |